Dear Mr. Haidar,
In the summary report, the reactive power from shunts and branch
charging are both injections, so the reactive power balance can be
expressed as ...
Qgen - Qload + Qshunt - Qloss + Qcharging = 0
--
Ray Zimmerman
Senior Research Associate
428-B Phillips Hall, Cornell University, Ithaca, NY 14853
phone: (607) 255-9645
On Dec 2, 2008, at 3:06 AM, ahmed haidar wrote:
Dear Prof. Ray Zimmerman,
First, I would like to thank the authors of this package for giving
us the chance to use it. I run the power flow for different cases
which are saved in the downloaded Matpower file and I found that the
reactive power in the summary report unbalanced. When computing the
power balance, this should hold:
Qgen - Qload - Qshunt - Qloss
Please, advise
Regards
A. Haidar