The reactive power cost in MATPOWER takes the same format as the real power 
cost. If there are ng generators and the gencost matrix has 2*ng rows, the 
first ng rows are used to specify the costs for real power and the last ng rows 
are the corresponding costs for reactive power.

-- 
Ray Zimmerman
Senior Research Associate
419A Warren Hall, Cornell University, Ithaca, NY 14853
phone: (607) 255-9645




On Nov 6, 2012, at 11:00 PM, Eezhamalar AT <[email protected]> wrote:

> Dear sir/mam,
>      In the manual of matpower, for opf problem, the cost function is based 
> on the real and reactive power functions. Real power function is explained 
> clearly. But how can we give the reactive power cost function. what is the 
> format. Please reply me soon. Thanks in advance
> 
> ---*Malar*

Reply via email to