The latest development version of MATPOWER has some utilities for finding 
islands and I have happy to send you the relevant functions off-list if you 
like. MATPOWER should handle a DC OPF with a system with islands just fine as 
long as each island has its own reference bus and each island has a feasible 
solution (e.g. sufficient generation to meet load without overloading lines).

-- 
Ray Zimmerman
Senior Research Associate
B30 Warren Hall, Cornell University, Ithaca, NY 14853
phone: (607) 255-9645





On Sep 8, 2013, at 10:18 PM, Jovan Ilic <[email protected]> wrote:

> 
> Does anybody know what happens if part of the system is 
> disconnected due to programmatically disabling branches.  
> I'd like to run DCOPF many times while possibly disconnecting 
> some of the lines. 
> 
> Thanks,
> Jovan Ilic

Reply via email to