Dear Ray
would you please send me the codes to find islands in the system?
thanks

Maximiliano
> The latest development version of MATPOWER has some utilities for finding
> islands and I have happy to send you the relevant functions off-list if
> you like. MATPOWER should handle a DC OPF with a system with islands just
> fine as long as each island has its own reference bus and each island has
> a feasible solution (e.g. sufficient generation to meet load without
> overloading lines).
>
> --
> Ray Zimmerman
> Senior Research Associate
> B30 Warren Hall, Cornell University, Ithaca, NY 14853
> phone: (607) 255-9645
>
>
>
>
>
> On Sep 8, 2013, at 10:18 PM, Jovan Ilic <[email protected]> wrote:
>
>>
>> Does anybody know what happens if part of the system is
>> disconnected due to programmatically disabling branches.
>> I'd like to run DCOPF many times while possibly disconnecting
>> some of the lines.
>>
>> Thanks,
>> Jovan Ilic
>
>


Reply via email to