I suppose it depends … do you want to minimize costs in the other areas as 
well, subject to fixed exchange schedules? If so, yes, I think working with 
toggle_iflims.m is best. If, on the other hand, you are only interested in 
minimizing cost in one area, with the dispatches fixed in other areas, then I 
think fixing those dispatches (PG=PMIN=PMAX) is sufficient to fix all of the 
interface flows as well and you don’t even need additional interface flow 
constraints.

-- 
Ray Zimmerman
Senior Research Associate
B30 Warren Hall, Cornell University, Ithaca, NY 14853
phone: (607) 255-9645



On Nov 26, 2013, at 8:10 PM, Henry Lin <[email protected]> wrote:

> Dear Dr. Zimmerman, 
> 
> Thanks a lot for your help. 
> 
> I want to minimize the cost of generation of one area subject to a fixed 
> value for the exchange between all the other areas. Shall I still work with 
> toggle_iflims.m as you suggested or you have some other suggestions? 
> 
> 
> Thanks a lot. 
> 
> Best,
> 
> Henry
> 
> 
> 
> 
> 2013/11/26 Ray Zimmerman <[email protected]>
> Sorry, somehow my previous reply never got sent …
> 
> So, what exactly do you want to optimize, if you are specifying the import 
> and export? Are you saying you want to minimize cost of generation in both 
> areas subject to a fixed value for the total exchange between the two areas? 
> If so, the best you can do is constrain the net flow (DC approximation) to 
> equal your specified value. The easiest thing is probably to start with the 
> code in toggle_iflims.m and modify it to use an equality constraint instead 
> of an inequality constraint on the interface flow.
> 
> -- 
> Ray Zimmerman
> Senior Research Associate
> B30 Warren Hall, Cornell University, Ithaca, NY 14853
> phone: (607) 255-9645
> 
> 
> 
> On Nov 26, 2013, at 10:43 AM, 车 <[email protected]> wrote:
> 
>> Hi Matpower users, 
>> 
>> Anybody have any ideas about how to calculate opf with the total import 
>> power and export power specified? 
>> 
>> 
>> Thanks a lot
>> 
>> Lin 
>> 
>> On Nov 25, 2013, at 8:59, Henry Lin <[email protected]> wrote:
>> 
>>> Dear all, 
>>> 
>>> I am trying to use OPF with area interchange being specified. I know how 
>>> much power is going to be import and export. 
>>> 
>>> How can I do it using Matpower?
>>> 
>>> 
>>> Thanks,
>>> Henry 
>> 
>> 
>> 
>> 
> 
> 