Charles Lepple wrote: > Could this be related to the "Evolution 650" bug mentioned in > mge-hid.c? (On the other hand, I suspect that if I added my model to > that function, it would only fix the battery.voltage.nominal)
I checked with Arnaud. The 'Pulsar Evolution' series doesn't support measurement of the 'battery.voltage(.nominal)' and instead returns what NUT regards as 'output.voltage(.nominal)'. I changed the 'mge-hid.c' subdriver to only use the 'UPS.PowerSummary.(Config)Voltage' for models/series that are known to use this as 'battery.voltage(.nominal)', so it should be fixed now (r1339). Best regards, Arjen _______________________________________________ Nut-upsdev mailing list [email protected] http://lists.alioth.debian.org/mailman/listinfo/nut-upsdev