On Tue, 3 Jul 2018, [email protected] wrote:
UPS is Eaton 5SC 500i.
Please do not know how to write some parameters permanently to UPS?
Read man ups.conf and man usbhid-ups and try setting the required values in
ups.conf. For example
[Eaton]
driver = usbhid-ups
port = auto
desc = "Eaton 5sc 500i"
offdelay = 30
ondelay = 40
lowbatt = 37
Roger