Ok, did an experiment -- the AAG TIA8540 (in the stainless canister) vs
Amprobe TH-2 benchtop meter:

AMPROBE        OWFS
C      %       C     %
17.2   31.2    19.0  29.0
18.5   32.3    20.22 28.4
----damp towel--------
16.3   82.3    18.5  74.5
15.6   86.1    18.1  78.3
15.2   88.7    17.4  81.7
14.8   90.0    16.7  83.6
14.4   92.8    15.9  89.9

It appears that the Stainless humidity sensor housing has some more thermal
mass and thus lags, but tracks closely.

Paul Alfille
-------------------------------------------------------------------------