Suzanne,
After discussing your problem with our telecoms expert, this is what he has
to say:
The best solution for such a high power consumption unit is to split the
power into 2 or 3 terminal blocks. This means you protect
Cc: sdeli...@unispherenetworks.com
Subject: RE: Field wiring terminal size
Suzanne,
Your best bet is to use components that have been previously evaluated for
field wiring, such as a UL Recognized terminal block for the + and - and a
UL Listed pressure terminal connector for the protective
Suzanne,
Your best bet is to use components that have been previously evaluated for
field wiring, such as a UL Recognized terminal block for the + and - and a
UL Listed pressure terminal connector for the protective earthing terminal;
of course both have to be suitable for the 100 A and the