Because the exceding generation is supplied by the swing bus. Normal power flow does not check power generation limits. El 17 feb. 2016 1:58 PM, "Bai, Wenlei" <[email protected]> escribió:
> Dear Ray, > > I tried to modified load of ‘case9’ to exceed the total generation > capacity purposely. > > To my surprise, power flow still converges. More specifically, the total > generator ‘on-line capacity’ is 820MW, while the ‘actual generation’ is > 920.8MW > > Why the actual generation can be larger than its capacity? > > > > Blessings, > Wenlei > > >