Because the exceding generation is supplied by the swing bus. Normal power
flow does not check power generation limits.
El 17 feb. 2016 1:58 PM, "Bai, Wenlei" <[email protected]> escribió:

> Dear Ray,
>
> I tried to modified load of ‘case9’ to exceed the total generation
> capacity purposely.
>
> To my surprise, power flow still converges.  More specifically,  the total
> generator ‘on-line capacity’ is 820MW, while the ‘actual generation’ is
> 920.8MW
>
> Why the actual generation can be larger than its capacity?
>
>
>