Wenlei, The power flow routine in MATPOWER does not enforce generation limits on real power. Exceeding the capacity does not necessarily imply a divergence of the power flow.
Shri From: <Bai>, Wenlei <[email protected]<mailto:[email protected]>> Reply-To: MATPOWER discussion forum <[email protected]<mailto:[email protected]>> List-Post: [email protected] Date: Wednesday, February 17, 2016 at 12:57 PM To: "[email protected]<mailto:[email protected]>" <[email protected]<mailto:[email protected]>> Subject: power flow question Dear Ray, I tried to modified load of ‘case9’ to exceed the total generation capacity purposely. To my surprise, power flow still converges. More specifically, the total generator ‘on-line capacity’ is 820MW, while the ‘actual generation’ is 920.8MW Why the actual generation can be larger than its capacity? Blessings, Wenlei