On 2021-07-31 20:29, Scott Ritchey via Mercedes wrote:
Good data point.  Thanks.

The LRA (locked rotor amps) on my 1.5T are 47.
I do not know why I can start it on a fast blow 15A breaker.
The install instructions demand a 20A HACR (slow blow HVAC) breaker.
Maybe the start kit helps?
What would really help is a 'slow start kit'.
Hard start kits don't reduce LRA, they just reduce the time for amps to drop. The 5-2-1 kits are considered the superior hard starts, but slow start makes it ramp up like an inverter drive.
https://www.cpsproducts.com/hvacr/5-2-1-compressor-saver/

_______________________________________
http://www.okiebenz.com

To search list archives http://www.okiebenz.com/archive/

To Unsubscribe or change delivery options go to:
http://mail.okiebenz.com/mailman/listinfo/mercedes_okiebenz.com

Reply via email to