Hi Uriel,

 

Outstanding!  Thank you sir, I’m off and running now.

 

Best regards,

russ

 

From: [email protected] 
[mailto:[email protected]] On Behalf Of Uriel Fernando 
Sandoval Pérez
Sent: Tuesday, December 8, 2020 11:07 PM
To: MATPOWER discussion forum
Subject: Re: infinite bus, 1 branch/1 gen

 

Hi Russ,

 

Attached is the file with some modifications. I obtained the same result you 
got manually.

 

================================================================================
|     System Summary                                                           |
================================================================================

How many?                How much?              P (MW)            Q (MVAr)
---------------------    -------------------  -------------  -----------------
Buses              2     Total Gen Capacity       0.0          49.1 to 49.1
Generators         2     On-line Capacity         0.0          49.1 to 49.1
Committed Gens     2     Generation (actual)     -0.0               9.4
Loads              0     Load                     0.0               0.0
  Fixed            0       Fixed                  0.0               0.0
  Dispatchable     0       Dispatchable          -0.0 of -0.0      -0.0
Shunts             0     Shunt (inj)             -0.0               0.0
Branches           1     Losses (I^2 * Z)         0.00              9.41
Transformers       0     Branch Charging (inj)     -                0.0
Inter-ties         0     Total Inter-tie Flow     0.0               0.0
Areas              1

                          Minimum                      Maximum
                 -------------------------  --------------------------------
Voltage Magnitude   1.154 p.u. @ bus 1          1.174 p.u. @ bus 2
Voltage Angle       0.00 deg   @ bus 1          3.31 deg   @ bus 2
P Losses (I^2*R)             -                  0.00 MW    @ line 1-2
Q Losses (I^2*X)             -                  9.41 MVAr  @ line 1-2

================================================================================
|     Bus Data                                                                 |
================================================================================
 Bus      Voltage          Generation             Load
  #   Mag(pu) Ang(deg)   P (MW)   Q (MVAr)   P (MW)   Q (MVAr)
----- ------- --------  --------  --------  --------  --------
    1  1.154    0.000*  -149.60    -39.69       -         -
    2  1.174    3.313    149.60     49.10       -         -
                        --------  --------  --------  --------
               Total:     -0.00      9.41      0.00      0.00

================================================================================
|     Branch Data                                                              |
================================================================================
Brnch   From   To    From Bus Injection   To Bus Injection     Loss (I^2 * Z)
  #     Bus    Bus    P (MW)   Q (MVAr)   P (MW)   Q (MVAr)   P (MW)   Q (MVAr)
-----  -----  -----  --------  --------  --------  --------  --------  --------
   1      1      2   -149.60    -39.69    149.60     49.10     0.000      9.41
                                                             --------  --------
                                                    Total:     0.000      9.41

 

Best,

 

Uriel

 

Reply via email to